Electrical System Design of a 15-Storey Hotel in Alabang, Muntinlupa City

Authors

  • Maria Catherine E. Simpao
  • Reynaldo H. Gomez Jr.
  • Michael John M. Villar

DOI:

https://doi.org/10.65138/ijprse.2026.v7i05.1277

Keywords:

Electrical Design, 15 Storey Hotel, Short Circuit Analysis, Harmonic Distortion, Protection Coordination, Arc-Flash Analysis, Philippine Electrical Code.

Abstract

This paper presents the comprehensive electrical system design for a 15-Storey Hotel located in Alabang, Muntinlupa City. The study focuses on creating a design that is safe, reliable, and cost-effective, adhering to the Philippine Electrical Code (PEC) and international standards (IEEE/NEC). The scope encompasses load computation, transformer sizing, and advanced system studies including harmonic analysis, short circuit calculations, protection coordination, and arc-flash hazard analysis. The system employs a 2000 kVA pad-mounted oil-type transformer stepping down 34.5 kV utility power to 0.230 kV. Results indicate that the proposed design maintains voltage drops within a 3-5% margin and ensures coordinated protection against fault currents up to 76.2 kA at the main bus.

Downloads

Download data is not yet available.

Downloads

Published

2026-05-12

How to Cite

Maria Catherine E. Simpao, Gomez Jr., R. H., & Villar, M. J. M. (2026). Electrical System Design of a 15-Storey Hotel in Alabang, Muntinlupa City. International Journal of Progressive Research in Science and Engineering, 7(05), 13–14. https://doi.org/10.65138/ijprse.2026.v7i05.1277

Issue

Section

Articles